PT PELANGI CAHAYA SEMPURNA

sql
Three Phase Failure Sequence Under & Overvoltage Relay
Hover to Zoom

Last Updated
28 Sep 2020
Country Origin
United Kingdom
Minimum Order
1 1

Specification of

Info : 021. 29023048 Email : pcs17a@gmail.com Wa: 08974906988

Phase Failure Three Phase Sequence Under & Overvoltage with Time delay

Specification :

  • Under and Over voltage monitoring
  • Monitors own three phase, 3-wire supply
  • Detects incorrect phase sequence and phase loss
  • Adjustable Trip levels and Time delay
  • SPDT Relay output
  • 17.5mm wide, DIN Rail mount
  • Monitoring function: Under/Over voltage
  • Monitored supply voltage*: 110V, 208V, 380V, 400V or 415VAC
  • Trip level: Under: 75 – 95%/Over: 105 – 125%
  • Hysteresis: ≈2%
  • Time delay: 0.2 – 10s
  • Output: SPDT 8A @ 250V (AC1)
  • Dimensions(mm): W:17.5 x H:89 x D:66.5

The product monitors it’s own three-phase supply and for the output relay to energise, all phases must be present, the phase sequence correct and the phase to phase voltages within the set Under/Over trip levels. If any of these conditions are not met, the relay will de-energise.